| 36KV compatible, 3-core multi-hole | Pressure-resistant multi-hole 3-core type. Protects cables from flashover and electrical induction up to 36KV. |
|---|---|
| High insulation, UV resistant, flame retardant | Excellent electronic insulation, anti-tracking, UV resistance, weather resistance, and flame retardancy. |
| Applications | Can be safely used for cable protection between power switchgear and voltage boxes. |
| Material | Cross-linked polyolefin |
|---|---|
| Shrink ratio | 2:1 to 3:1 |
| Shrink start temperature | 110℃ |
| Operating temperature range | -55℃ to 105℃ |
| Standard color | Reddish brown |
| Property | Test Method | Value |
|---|---|---|
| Tensile Strength | ASTM D2671 | >8MPa |
| Elongation at Break | ASTM D2671 | ≧550% |
| Tensile Strength / Elongation after Heat Aging | ASTM D2571 (120℃, 168 hours) | >10MPa / >450% |
| Dielectric Strength | IEC 243 | ≧20kV/mm |
| Volume Resistivity | IEC 93 | ≧10¹³ Ω・cm |
| Water Absorption | ISO 62 (23℃, 14 days) | ≧1% |
| Tracking Resistance | ASTM D2303 | None |
*The above data represents typical values and is not a guarantee.
| Part No. | D Inner Diameter - Overall (mm) | D1 Inner Diameter - Multi-hole section (mm) | L Overall Length (mm) |
L1 Multi-hole section length (mm) |
||
|---|---|---|---|---|---|---|
| Before Shrinkage | After Shrinkage | Before Shrinkage | After Shrinkage | |||
| TSCM-3-6020 | 60 | 24 | 25 | 8 | 180 | 45 |
| TSCM-3-8036 | 80 | 38 | 35 | 11 | 210 | 57 |
| TSCM-3-11048 | 110 | 50 | 46 | 17.5 | 250 | 65 |
| TSCM-3-12555 | 125 | 57 | 55 | 20 | 260 | 57 |
| TSCM-3-14070 | 140 | 70 | 62 | 26 | 280 | 70 |
Unit: mm